What should I pay attention to when choosing an evaporator for an ultra-low temperature chiller?
The evaporator in the ultra-low temperature chiller is one of its four major components, so performance is more important.
The selection of ultra-low temperature chillers needs to pay attention to the influence of liquid level on the evaporation temperature. Due to the influence of the height of the refrigerant liquid column, the evaporation temperature at the bottom of the flooded evaporator is higher than the evaporation temperature of the liquid surface. The evaporation temperature of different refrigerants at different liquid levels is affected differently by the height of the static liquid. Regardless of the refrigerant, the lower the evaporation temperature of the liquid surface, the greater the influence of the hydrostatic height on the evaporation temperature. Therefore, only when the evaporation pressure is high, the influence of the hydrostatic height on the evaporation temperature can be ignored. When the evaporation temperature is low, it cannot be ignored. In other words, it becomes uneconomical to use a flooded evaporator at this time.

If the evaporation temperature is lower than the freezing temperature of the refrigerant, the refrigerant may freeze. In the subsequent flow of the refrigerant, the temperature of the refrigerant is low, and the possibility of freezing is high. When water is used as the refrigerant, theoretically, the temperature of the inner wall of the tube can be as low as 0°C. However, for safety reasons, the temperature of the inner wall of the pipe at the outlet end of the next process is usually kept above 0.5°C. In the case of brine as the refrigerant, according to the same principle, the temperature of the inner wall of the tube should be higher than the freezing temperature of the refrigerant by more than 1°C.
When the refrigerant flows through the evaporator, pressure loss is caused, which will inevitably make the pressure p2 of the refrigerant at the outlet of the evaporator be lower than the pressure p1 at the inlet, thereby reducing the suction pressure of the compressor, resulting in a decline in the refrigeration capacity.
According to different models, the choice of evaporator is different. For example, the box-type small ultra-low temperature chiller uses a water tank coil type evaporator; the open-type small ultra-low temperature chiller and the screw-type small ultra-low temperature chiller use shell and tube Type evaporator; for acid and alkali resistant ultra-low temperature chillers, you can choose titanium tube evaporator or stainless steel plate exchanger; there are many options, of course, it can be customized according to user needs.
The ultra-low temperature chiller evaporator is generally designed and equipped by the ultra-low temperature freezing test manufacturer. It is recommended that users check the configuration problems when choosing the ultra-low temperature chiller manufacturer.
Recommandations connexes
-
Attention points for daily inspection of low temperature control equipment at minus 30℃
1092The low temperature control equipment at minus 30 degrees Celsius is a refrigeration unit or also called a refrigeration unit. The difference from the chiller is the temperature range. It is a commonly used low-temperature equipment in the industr...
Voir les détails -
Cooling fin cleaning instructions for 20 freezers
1206As one of the main accessories of the 20-piece freezer, the heat-dissipating fins are very important. Therefore, the cleaning of the heat-dissipating fins is also very important. How to clean them? The fins of the freezer are also called finned co...
Voir les détails -
Refrigerating Output of Low Temperature Cooling Circulator
928The refrigerating output of low temperature cooling circulator varies with different working conditions. So, when the process calculation is carried out at the beginning, it is necessary to set an allowance for the refrigerating output of the heat...
Voir les détails -
Burning machine phenomenon in small high and low temperature integrated machine
897The small high-low temperature integrated machine is used for the temperature control of the connected reactor in the pharmaceutical, chemical and other industries. Once the burning phenomenon occurs during operation, we need to pay special attent...
Voir les détails