Solutions aux défaillances des refroidisseurs à circulation profonde dues à la haute pression
Deep-circulation chillers are process cold sources used in the production and processing of chemical and pharmaceutical intermediates, petrochemicals, machinery, medicine, electronics, new materials, aerospace, optoelectronic technology, and new energy. But how to deal with the high-pressure failure of the deep-circulation chiller?

1. The cooling water temperature is too high, and the condensing effect is not good, resulting in high pressure failure
The rated working conditions of cooling water required by deep-circulation chillers, high water temperature and poor heat dissipation, will inevitably lead to high condensing pressure. This phenomenon often occurs in high-temperature seasons. It can be solved by adding more storage tanks.
2. The cooling water flow is insufficient, and the rated water flow is not reached, resulting in a high-pressure fault
The main performance is that the pressure difference between the inlet and outlet water of the unit becomes smaller and the temperature difference becomes larger. The reason for the insufficient water flow is the lack of water in the system or the presence of air. The solution is to install an exhaust valve at the height of the pipeline to exhaust; the pipeline filter is blocked or the selection is too fine, and the water permeability is limited. You should choose a suitable filter and Clean the filter regularly; the water pump is small and does not match the system.
3. High pressure failure due to fouling or clogging of the condenser
Its performance is that the pressure difference and temperature difference between the inlet and outlet of the deep circulation chiller become larger, and the upper and lower temperatures of the condenser are very high when you touch the condenser by hand, and the condenser outlet copper pipe is hot. The unit should be backwashed regularly, and chemical cleaning and descaling should be carried out if necessary.
4. The refrigerant mixed with air, nitrogen and other non-condensable gases causes high pressure failure
This situation generally occurs after maintenance, and the vacuum is not applied. It can only be drained, re-evacuated, and recharged with refrigerant.
5. False alarms caused by electrical faults produce high-voltage faults
Because the high-voltage protection relay is damp, poorly contacted or damaged, the unit electronic board is damp or damaged, and the communication failure causes a false alarm. For this kind of false fault, the HP fault indicator on the electronic board is often off or slightly bright, the high-voltage protection relay is manually reset invalid, or disappears automatically, the running current of the compressor is normal, and the suction and discharge pressures are also normal.
6. Too much refrigerant charge causes high pressure failure
This situation generally occurs after maintenance, and it is manifested as high suction and exhaust pressure and balance pressure, and high compressor operating current. It should be vented according to the suction and discharge pressure, balance pressure and operating current under rated conditions until normal.
Recommandations connexes
-
Analyse des prix des chambres d'essais à haute et basse température
1064As the saying goes, “ You get what you've paid. ” The price of the high low temperature test chamber is related to the quality of its configuration. The technology of Wuxi LNEYA itself is priceless. In the test chamber industry, the high low tempe...
Voir les détails -
Soultion de contrôle de la température pour les solutions de nettoyage des wafers dans l'industrie des semi-conducteurs
1244Avec le développement rapide de la technologie des semi-conducteurs, les exigences en matière de plaquettes sont de plus en plus élevées, ce qui rend la propreté des surfaces des plaquettes de plus en plus importante pour la fabrication des dispositifs à semi-conducteurs. Dans le processus de fabrication des gaufres, la propreté des surfaces est de plus en plus importante pour la fabrication des dispositifs à semi-conducteurs.
Voir les détails -
Introduction to the structure and application of industrial refrigerators
998Industrial refrigerators are usually called industrial refrigerator boxs, and low-temperature freezers.Temperature range: -150℃~-20℃. Industrial refrigerators can be divided into vertical and horizontal types. Most of them use imported compressors...
Voir les détails -
Large industrial freezer structural stability instructions
1253Large industrial refrigerators are used in the current industry. In order to maintain a smooth operation, the related structure also needs to maintain a stable state in order to stabilize and operate efficiently. The main structure of Wuxi Guanya ...
Voir les détails