Maintenance Method Of Ultra Low Temp Chiller Refrigeration System
Le ultra low temp chiller refers to the refrigeration unit whose chilled water temperature reaches below minus 35℃. The unit adopts two-stage compression refrigeration, and the combination of the scroll compressor and the piston compressor is used to manufacture a freezing source of minus 35℃ or even minus 60 ℃, to meet the requirements of the production process, to ensure the normal and smooth production.
Firstly, the leak detection of ultra low temp chiller system.
1. The refrigerant side of the unit has undergone a strict leak detection process during the factory and commissioning process.
2. After the unit is running, check the high-pressure part with the leak detector to ensure the tightness of all connections.
3. If a leak is found, it should be disposed of immediately. In general, the connection of the nano or flange bolts can be used to eliminate the leaks, but there is also the possibility that the refrigerant be recovered and then the leaks must be treated. Such as the leakage of welded joints.
Second, the system’s pressure leak detection.
The standard pressure leak detection steps for ultra low temp chillers are as follows:
1. Fill a small amount of R-22 gas to a system pressure of 2PSIG.
2. Fill the system with nitrogen to 25~50 PSIG. Make sure the pressure reaches all parts of the system. The oil valve can be opened slightly, and the leak detector is used to check whether there is refrigerant.
3. Check each joint and weld, and try to be careful and spend as much time as possible. The leak detection equipment used must be sensitive and reliable.
4. Open the top bleed valve of the evaporator and condenser to confirm that no refrigerant has been detected. If refrigerant is found, the end cap should be removed to remove the internal leak.
5. Confirm that the system is completely sealed, and the gas is released from the system at an appropriate flow rate from the filling valve to perform a certain purging action.
Thirdly, vacuuming and drying of ultra-low temperature chiller system.
1. Connect the high efficiency vacuum pump and the mercury vacuum gauge in series with the filling valve of the system.
2. Open all valves of the system that connect the valve, the suction valve and the vacuum gauge. Confirm that all valves that pass through the atmosphere are closed.
3. Start the vacuum pump and pump the vacuum to 5mmHg.
4. If there are conditions, 50oC of hot water can be introduced into the system to accelerate the evaporation of the system’s memory and improve the dryness.
Recommandations connexes
-
Le LNEYA a pris l'initiative de permettre des audits en ligne et en direct.
1330Les bons produits proviennent d'un processus de fabrication strict. En mars 2020, LNEYA a pris l'initiative d'adopter les méthodes de supervision des nuages et d'inspection des usines, en se concentrant sur l'affichage du dispositif de contrôle de la température du chauffage par réfrigération de LNEYA, de l'unité de contrôle de la température (TCU) et de l'unité de contrôle de la température de l'usine.
Voir les détails -
Ultra-low temperature freezing manufacturer analyzes the cause of blockage in refrigeration system
1308With the continuous development of technology, ultra-low temperature refrigeration technology is also constantly developing, and manufacturers are also increasing. Of course, the technology of different manufacturers is different. Once the refrige...
Voir les détails -
Application and working principle of water-cooled chiller
946Application and working principle ofwater-cooled chillerThe water-cooled chiller is a kind of LNEYAindustrial low-temperature refrigerator in Wuxi Guanya. A single compressor canachieve -152 degrees Celsius cooling and cooling. Equipment power,...
Voir les détails -
What should be paid attention to when placing the thermostat system?
951There are certain differences in the size and performance of the high and low temperature thermostat systems produced by different manufacturers. The user needs to pay attention to how it is placed when placing it after purchase, otherwise it will...
Voir les détails