Three Common Failures Of Air Cooled Screw Chiller
Three Common Failures Of Air Cooled Screw Chiller
1. Communication Failure:
Computer controller controls various modules by telecommunication lines and total interface board, so the main cause of communication failure is poor contact or break of communication lines, especially the interface oxidation and damp of the interface. Also, the failure of unit electronic board or total interface board, incorrect choice of address dial code switch and power failure can cause the communication failure.
2. Low Voltage Failure:
The low suction pressure of the compressor results in low pressure protection relay action. The suction pressure of the compressor reflects the evaporation pressure, whose the normal value should be 0.4~ 0.6mpa, and the protection value is set to 0.2mpa. Low suction pressure causes low return air volume and insufficient cooling capacity, resulting in waste of electrical energy and the heat dissipation of the motor of gas cooled compressor which is easy to damage the motor.
3. High Voltage Failure:
High exhaust pressure of compressor results in high voltage protection relay action. The compressor exhaust pressure reflects condensation pressure whose normal value should be 1.4~ 1.6mpa, and the protection value is set to 2.0mpa. If the pressure is too high for a long time, it will cause too large of the current of compressor, which is easy to burn the motor and damage the compressor exhaust valve disc.
Recommandations connexes
-
How to Choose Water Chiller Units in Small Factories
1152Professional water chiller factory said that the quality of equipment can be seen from the three main components of small water chiller units. The most important one is the compressor, which is the heart of the unit and the most critical component...
Voir les détails -
High-power industrial refrigerator evaporator maintenance precautions
1068High-power industrial refrigerators are used in industrial cold processing. Evaporators in high-power industrial refrigerators are one of the most important components and one of the factors affecting the cooling effect of high-power industrial re...
Voir les détails -
Quelles sont les caractéristiques et le champ d'application des circulateurs frigorifiques cryogéniques? ?
1174Spécialisée dans le développement et la production de circulateurs frigorifiques à basse température, la plage de température de réfrigération s'étend de -120 degrés à -30 degrés. Aujourd'hui, examinons les caractéristiques des circulateurs frigorifiques à basse température...
Voir les détails -
Instructions for cold assembly of bearings in ultra-low temperature industrial refrigerators
997The refrigeration system of ultra-low temperature industrial refrigerators generally adopts the working principle of cascade refrigeration, and two fully enclosed compressors are used as high and low temperature compressors. The copper tube of the...
Voir les détails