How to troubleshoot the failure of the material aging test chiller?
Regular maintenance work for the material aging test chiller, and troubleshooting is also very important.
1. Exhaust at double high pressure, heat dissipation may be problematic.
When it is detected that the high and low pressure of the system are higher than normal, it is usually because there is air in the system or excessive refrigerant is added. At this time, it is necessary to re-evacuate and add an appropriate amount of refrigerant to solve the problem. However, there is another situation, that is, poor heat dissipation, especially when the ambient temperature is relatively high, which often leads to worse heat dissipation. The cause of this failure is generally that the heat sink is blocked, dirty, and the speed of the heat dissipation fan is not enough.
2. Refrigerant with low pressure loss, otherwise the system will be blocked.
When the high and low pressures are both low, there are two possibilities:
(1) If the system is blocked, the blocked part will produce throttling, and there will be a significant temperature difference in the throttling part, and the problem can be found by feeling it with your hands.
(2) The leakage of refrigerant leads to insufficient refrigerant. This situation is more common. At this time, the material aging test cooler detector must be used to find out the leaking location and perform replacement.
3. Low pressure, high pressure, low pressure, replace the compressor.
When the material aging test cooler pressure gauge detects that the low pressure is higher than normal, and the high pressure is lower than normal, at this time, it is recommended that the chiller refrigeration cannot achieve the effect of the normal material aging test refroidisseur. The reason is likely to be the wear and tear in the material aging test refroidisseur pump, resulting in a drop in power. At this time, it is often necessary to replace the compressor to solve the problem.
4. There is water vapor in the meter shake system, so it must be changed when it is timed out.
When the material aging test cooling machine system is working, if the pressure gauge needle keeps shaking, it means that there is moisture in the system. To solve this problem, it is generally necessary to re-evacuate, and the pumping time must be no less than 15 minutes. If necessary, the drying bottle needs to be replaced to drain the water in the system.
Recommandations connexes
-
Solutions aux défaillances des refroidisseurs à circulation profonde dues à la haute pression
1000Les refroidisseurs à circulation profonde sont des sources de froid utilisées dans la production et le traitement de produits chimiques et pharmaceutiques intermédiaires, la pétrochimie, les machines, la médecine, l'électronique, les nouveaux matériaux, l'aérospatiale, la technologie optoélectronique et les nouveaux...
Voir les détails -
How to use a multimeter to test the components of the chip test temperature control machine?
1031The chip test temperature controller is used for IC, CPU, GPU, DPU, BGA, FCBGA, LGA, QFN, QFP, CSP, WLCSP, Bare Die, and other Device Under Test. So, how to use a multimeter for these commonly used components What about testing? For electronic com...
Voir les détails -
Quelles sont les caractéristiques de la réfrigération des refroidisseurs industriels ?
1189If there is a high temperature difference between the inlet and outlet water, then a large external tank will be used to store cold water. In this case, the cooling water will not be directly from the cooler application. Deep into the outside of t...
Voir les détails -
Description of the action of the filter in the ultra-low temperature compressor unit
1117In order to stabilize the operation of the ultra-low temperature compressor unit, the performance of the compressor is very important, and in addition to the compressor, the filter is also important. In order to maintain normal operation, it is ne...
Voir les détails