Centre d'information

SUNDI -10℃~150℃
  • Capacité de refroidissement0.5kW~10kW
  • Capacité de chauffage0.5kW~10kW
  • RéfrigérantR134A/R1234yf
  • Poids115KG~300KG

Air-cooling & Water-cooling

Détails de la configuration

Modèle KRYZ-475
KRYZ-475W
KRYZ-4A15W KRYZ-4A25W
Plage de température -40℃~+100℃
Précision du contrôle de la température ±0.1℃ ±0.1℃ ±0.1℃
Retour d'information sur la température Pt100 Pt100 Pt100
Affichage de la température 0.01k 0.01k 0.01k
Flow output 1~25 L/min 1~25 L/min 1~25 L/min
About traffic description When the temperature is below -30 degrees, the flow rate is controlled within 80% of the maximum value.
Flow control accuracy ±0.1 L/min ±0.1 L/min ±0.1 L/min
Affichage de la pression Using pressure sensor, the pressure is displayed on the touch screen, and the pressure control can be adjusted from 0.2bar to 2.5bar
Heating capacity kW 7.5 15 25
Cooling capacity kW 100℃ 7.5 15 25
  20℃ 7.5 15 25
  0℃ 7.5 15 25
  -20℃ 4.5 10 16
  -35℃ 1.8 4 6.5
Compresseur Inverter scroll compressor
Méthode d'étranglement Soupape d'expansion électronique
Séparateur d'huile Emerson
Filtre déshydrateur Danfoss
Évaporateur Échangeur de chaleur à plaques
Pompe de circulation Variable frequency magnetic drive pump
Entrée, affichage 7-inch color touch screen, PLC controller
Programming 5 programs can be compiled, each program can compile 40 steps
Communications Modbus RTU protocol RS485 interface, optional CAN communication bus, Ethernet TCP/IP protocol
Protection de la sécurité It has self-diagnosis function; refrigerator overload protection; high pressure switch, overload relay, thermal protection device, low liquid level protection, high temperature protection, sensor fault protection and other safety protection functions.
Système The entire system is a fully closed system. There will be no water vapor at high temperatures and no absorption of moisture in the air at low temperatures. The system will not cause pressure to rise due to high temperatures during operation, and will automatically replenish heat transfer media at low temperatures.
Réfrigérant R404A/ R507C
Taille de l'interface G3/4 G3/4 G3/4
Water cooled @25℃ 2500L/H
ZG3/4
4000L/H
ZG1
6000L/H
DN32
Condenseur refroidi à l'eau The water equipment condenser of this product adopts plate heat exchanger, which requires water supply from chiller or low hardness tap water, and requires water purification filter
Air cooled condenser Échangeur de chaleur à microcanaux / /
Power supply 380V50HZ 14kW 25kW 38kW
Dimensions en cm 55*85*175 70*100*175 80*120*185
Poids 280kg 360 kg 620kg
Standard Automatic antifreeze filling system, automatic liquid recovery system
En option 220V 60HZ three-phase 400V 50HZ three-phase 440V 60HZ three-phase
En option Temperature extended to -40℃~+135℃
Remarque The external circulation pipeline should have a diameter of DN15 or DN20. The pipeline needs to be well insulated, and high-temperature resistant rubber and plastic insulation pipes can be used.
Matériau de la coque Cold rolled sheet spraying (standard color 7035)

Modèle KRYZ-475W/2T KRYZ-4A15W/2T KRYZ-4A25W/2T
Plage de température -40℃~+100℃
Précision du contrôle de la température ±0.1℃ ±0.1℃ ±0.1℃
Retour d'information sur la température Pt100 Pt100 Pt100
Affichage de la température 0.01k 0.01k 0.01k
Flow output 1~25 L/min 1~25 L/min 1~25 L/min
About traffic description When the temperature is below -30 degrees, the flow rate is controlled within 80% of the maximum value.
Flow control accuracy ±0.1 L/min ±0.1 L/min ±0.1 L/min
Fluid output groups 2 groups 2 groups 2 groups
Pressure control per group 0.2bar~2.5bar 0.2bar~2.5bar 0.2bar~2.5bar
Flow Pressure Description The device can control flow or pressure independently. Different solutions are required for simultaneous control (customization required)
Heating capacity kW 7.5*2 10*2 15*2
Cooling capacity kW 100℃ 7.5*2 15*2 25*2
20℃ 7.5*2 15*2 25*2
0℃ 7.5*2 15*2 25*2
-20℃ 4.5*2 8.5*2 14*2
-35℃ 1.8*2 4*2 6.5*2
Compresseur Inverter scroll compressor
Méthode d'étranglement Soupape d'expansion électronique
Séparateur d'huile Emerson
Filtre déshydrateur Danfoss
Évaporateur Échangeur de chaleur à plaques
Pompe de circulation Variable frequency magnetic drive pump
Flow rate, pressure Electromagnetic flowmeter, pressure value 4~20mA
Entrée, affichage 7-inch color touch screen, PLC controller
Communications Modbus RTU protocol RS485 interface, optional CAN communication bus, Ethernet TCP/IP protocol
Protection de la sécurité It has self-diagnosis function; refrigerator overload protection; high pressure switch, overload relay, thermal protection device, low liquid level protection, high temperature protection, sensor fault protection and other safety protection functions.
Système The entire system is a fully closed system. There will be no water vapor at high temperatures and no absorption of moisture in the air at low temperatures. The system will not cause pressure to rise due to high temperatures during operation, and will automatically replenish heat transfer media at low temperatures.
Réfrigérant R404A/R507C/R125/N40 four refrigerants can be used
External output interface size There are 2 sets of inlet and outlet ports, G3/4
Water cooled @25℃ 4000L/H
ZG1
8000L/H
DN32
12000L/H
DN40
Condenseur refroidi à l'eau The water equipment condenser of this product adopts plate heat exchanger, which requires water supply from chiller or low hardness tap water, and requires water purification filter
Dimensions en cm 80*120*185 100*150*185 200*145*205
Power supply 380V50HZ 28kW 45kW 70kW
Poids 660KG 850 kg 1350kg
Standard Automatic antifreeze filling system, automatic liquid recovery system
En option 220V 60HZ three-phase 460V 60HZ three-phase
En option Temperature extended to -40℃~+135℃
Remarque The external circulation pipeline should have a diameter of DN15 or DN20. The pipeline needs to be well insulated, and high-temperature resistant rubber and plastic insulation pipes can be used.
Matériau de la coque Cold rolled sheet spraying (standard color 7035)

Peut répondre aux besoins de refroidissement direct/chauffage direct pour les essais et les tests des batteries et des véhicules. Il est principalement utilisé pour tester la capacité de refroidissement et de chauffage. Il utilise un compresseur à fréquence variable dont la puissance est réglable et un ventilateur à fréquence variable dont la vitesse et la dissipation de chaleur sont réglables. Grâce à des capteurs de température, de pression et de débit de haute précision et à un logiciel intégré, il peut calculer la capacité d'échange thermique en temps réel, recycler et remplir automatiquement le réfrigérant, etc. Il peut répondre aux besoins de batteries de différentes tailles.

Envoyez-nous un message sur le produit
*
*
正在提交中....
提交成功!
提交失败!请稍后再试
邮箱错误!
电话错误!

Ces produits peuvent également vous intéresser

  • Onduleur LTZ série M"      /&gt;<figcaption><span>APPLICATIONS Convient pour l'application à l'objet de régulation de la température cible qui dispose déjà d'un réservoir de stockage du froid et d'une pompe de circulation, et le fluide est transporté dans l'unité de régulation de la température de réfrigération de la série LTZ M par l'intermédiaire de l'unité de régulation de la température de réfrigération...</span></figcaption></figure></a></div><div class=Onduleur LTZ série M

    APPLICATIONS Convient pour l'application à l'objet de régulation de la température cible qui dispose déjà d'un réservoir de stockage du froid et d'une pompe de circulation, et le fluide est transporté dans l'unité de régulation de la température de réfrigération de la série LTZ M par l'intermédiaire de l'unité de régulation de la température de réfrigération...

  • LN -60°C~ -10°C"      /&gt;<figcaption><span>适用范围 Caractéristiques du produit 产品参数 Paramètres du produit 行业应用 APPLICATION 航空航天材料|试验装置控温解决方案 在航空航天领域,材料的性能直接关系到飞行器的安全、可靠性和...</span></figcaption></figure></a></div><div class=LN -60°C~ -10°C

    适用范围 Caractéristiques du produit 产品参数 Paramètres du produit 行业应用 APPLICATION 航空航天材料|试验装置控温解决方案 在航空航天领域,材料的性能直接关系到飞行器的安全、可靠性和...

  • LT -80℃~-20℃"      /&gt;<figcaption><span>Il peut garantir un fonctionnement continu pendant 24 heures Réfrigération par circulation d'éthylène glycol mélangé à de l'eau 1. Peut utiliser de l'éthylène glycol mélangé à de l'eau pour la réfrigération par circulation, ce qui permet d'économiser les ressources....</span></figcaption></figure></a></div><div class=LT -80℃~-20℃

    Il peut garantir un fonctionnement continu pendant 24 heures Réfrigération par circulation d'éthylène glycol mélangé à de l'eau 1. Peut utiliser de l'éthylène glycol mélangé à de l'eau pour la réfrigération par circulation, ce qui permet d'économiser les ressources....