Troubleshooting of Common Faults of Industrial Water Chiller
As we all know, with the rapid development of modern industrial technology, in order to improve production efficiency, improve product quality and reduce consumption costs, the demand for temperature control equipment in the process is higher and higher, but there are more and more product quality problems about some industrial water chillers, So we simply analyze some common problems about industrial water chillers.

Abnormal temperature at the inlet and outlet of cooling water: the water temperature at the inlet of condenser is too high (higher than 32 ℃), first check whether the fan of cooling tower can be reversed (there are such examples in practical engineering). Then, after technical demonstration and on the premise of feasibility, adjust the blade angle of the fan to improve the air volume of the fan.
Another phenomenon often occurs in the system with multiple cooling towers in parallel. When the local load is running, the temperature difference between the inlet and outlet of the condenser is too small. It is necessary to check whether each cooling tower has been equipped with an electric valve, or whether the set electric valve fails to form a cooling water bypass, which can not be cooled completely.
The differential pressure at the inlet and outlet of cooling water is abnormal. According to the relevant refrigeration theory, the heat release of the condenser will directly affect the refrigeration capacity. Therefore, the user should first check the cooling water system based on the pressure loss value on the main engine. If the pressure difference obtained from the value of the pressure gauge at the inlet and outlet greatly exceeds the normal value, it indicates that there are sundries at the inlet of the condenser.
Recommandations connexes
-
Comment le conducteur d'essai de la batterie du véhicule électrique est-il mis à la terre ?
979If the electric vehicle battery test is not isolated between the AC power source and the drive DC bus (such as a transformer), do not connect the non-isolated port of the DC bus or the ground of the non-isolated signal to the ground, which may res...
Voir les détails -
Organic waste gas treatment device noise description
1411With the increasingly stringent environmental requirements, various manufacturers have paid more and more attention to their own organic waste gas treatment. LNEYA organic waste gas treatment equipment specializes in the treatment of various organ...
Voir les détails -
Sélection et entretien d'un refroidisseur à ultra-basse température
925Aujourd'hui, un client est venu s'enquérir de notre besoin d'un petit refroidisseur d'eau de laboratoire. La condition de travail spécifique est de réduire les matériaux dans le réacteur en acier inoxydable de 20L de la température normale à moins 30 ℃ en plus d'une heure. Ce p...
Voir les détails -
Energy-efficient high and low temperature circulation box description
1148With the efficient development of the pharmaceutical and chemical industry, environmental pollution is also the subject of more attention. To this end, LNEYA actively responds to environmental protection, produces energy-efficient and high-tempera...
Voir les détails